RecommendedThe four quantities
Every electrical circuit can be described with four numbers. Voltage, in volts, is the electrical pressure pushing current around the circuit. Current, in amps, is how much charge flows. Resistance, in ohms, is how strongly the circuit opposes that flow. Power, in watts, is the rate at which energy is used. Know any two and the other two are fixed.
Rearranged: I = V / R, R = V / I, P = I squared x R, and P = V squared / R. Every combination this calculator solves comes from these two equations.
A worked example
A 1,500 watt space heater plugs into a 120 volt outlet. The current is 1,500 / 120, which is 12.5 amps. The heater's resistance when hot is 120 x 120 / 1,500, which is 9.6 ohms. A space heater runs for hours at a time, so it counts as a continuous load, and a continuous load may use only 80 percent of a breaker's rating. 80 percent of a 15 amp breaker is 12 amps, which 12.5 amps exceeds. The smallest breaker that handles it as a continuous load is 20 amps, at 63 percent of the rating.
The 80 percent rule
The National Electrical Code treats any load expected to run at its maximum current for three hours or more as continuous. A breaker protecting a continuous load must be sized at 125 percent of that load, which is the same thing as saying the load may use no more than 80 percent of the breaker. The reason is heat. A breaker and its wiring warm up under a long, steady load, and the margin keeps them from nuisance tripping or running hot.
Typical continuous loads include space heaters, water heaters, electric vehicle chargers, pool pumps and heat tape. A toaster, a microwave or a power saw runs for minutes, not hours, and is treated as non continuous, so it may use the full breaker rating. Choose the load type in the calculator to apply the right limit.
Watts to amps and amps to watts
The two conversions people look up most are simple versions of P = V x I. Amps are watts divided by volts, and watts are volts times amps. At 120 volts, every 120 watts is one amp. At 240 volts, every 240 watts is one amp, which is why large appliances such as ranges, dryers and water heaters run on 240 volts: the same power needs half the current, and half the current needs a smaller wire.
Where Ohm's law is not the whole story
The calculator assumes a direct current circuit or an alternating current circuit with a purely resistive load, such as a heater, a kettle or an incandescent bulb. Motors, compressors, transformers and many electronic power supplies are not purely resistive. They have a power factor below 1, which means the current is higher than watts divided by volts would suggest. For those, real power is V x I x power factor, and the nameplate current, not a calculated one, is the figure to size a circuit by. Motors also draw several times their running current for a moment when they start.
Three phase supplies, found in commercial and industrial buildings, follow P = square root of 3 x V x I x power factor for a balanced load. That is outside what this calculator covers.
Resistance and wire
Every wire has a little resistance, and resistance times current is a voltage lost along the run. On a long circuit that loss can be large enough to dim lights or stall a motor. The voltage drop calculator works this out for a given wire size and length, and is the next step after you know the current a load draws.
Safety
- These results are arithmetic, not an inspection or a design. Electrical work is regulated, and in most places adding or changing circuits requires a licensed electrician and a permit.
- Always switch off and verify a circuit is dead with a tester before touching conductors.
- Never exceed the rating printed on a plug, an extension cord or a power strip.