Wire Size Calculator

Calculate electrical wire gauge (AWG) based on NEC Table 310.16 ampacity ratings and maximum 3% voltage drop over distance for copper and aluminum conductors.

✓ Imperial and metric✓ Package size results✓ Private by design
01
Enter your projectCircuit load and run distance
02
Your resultUpdates as you type
Recommended wire gauge 0

Drop percentage0

of supply voltage

Minimum ampacity0

NEC Table 310.16 rating

Buy this0

Rounded up to whole packages.

Minimum AWG by ampacity0
Minimum AWG for voltage drop0
Conductor circular mils0
Volts lost at load0
Selected AWG conductor0
How this was calculated
Advertisement

How wire gauge sizing works under the NEC

Selecting the correct wire size for an electrical circuit is governed by two distinct criteria in the National Electrical Code (NEC):

  1. Ampacity (Thermal Limit): The conductor must have sufficient cross-sectional area to carry continuous and non-continuous circuit current without heating the insulation beyond its temperature rating (NEC Table 310.16).
  2. Voltage Drop (Efficiency & Performance): On long circuit runs, conductor resistance causes voltage to drop before reaching the electrical load. NEC Informational Notes 210.19(A) and 215.2(A)(1) recommend that voltage drop should not exceed 3% on branch circuits, or 5% across both feeder and branch circuits combined.

The correct wire gauge is always the larger of the two sizes required by ampacity and voltage drop.

The formulaVoltage Drop (Single Phase) = (2 x Distance ft x Amps x Resistance per 1,000 ft) / 1,000

Three Phase Voltage Drop = (1.732 x Distance ft x Amps x Resistance per 1,000 ft) / 1,000. Resistance values come from NEC Chapter 9 Table 8.

A worked wire gauge example

Suppose you are running a 120-volt, 20-amp single-phase circuit to a detached workshop or shed located 150 feet away using copper conductors, aiming for a maximum 3% voltage drop.

  • Ampacity check: A 20-amp circuit breaker requires a minimum 12 AWG copper wire (rated 25 amps at 75 deg C terminal rating).
  • Resistance of 12 AWG copper: 1.93 ohms per 1,000 feet (NEC Table 8).
  • Voltage drop on 12 AWG: (2 x 150 ft x 20A x 1.93 ohms) / 1,000 = 11.58 Volts.
  • Drop percentage: (11.58V / 120V) x 100 = 9.65%. This vastly exceeds the 3% limit (3.60V max). Connected power tools would overheat and stall.
  • Upsizing to 10 AWG (1.21 ohms/kft): (2 x 150 x 20 x 1.21) / 1000 = 7.26V (6.05% drop - still too high).
  • Upsizing to 8 AWG (0.764 ohms/kft): (2 x 150 x 20 x 0.764) / 1000 = 4.58V (3.82% drop - close, but still over 3%).
  • Upsizing to 6 AWG (0.491 ohms/kft): (2 x 150 x 20 x 0.491) / 1000 = 2.95V (2.46% drop).
  • Final selection: Use 6 AWG copper wire. Voltage drop is reduced to 2.46%, delivering 117.05 volts to the shed.

Standard AWG ampacity and properties table

Extracted from NEC Table 310.16 and Chapter 9 Table 8 for copper and aluminum conductors:

Wire Gauge60 deg C Amp75 deg C Amp90 deg C AmpCopper Ohms/kftAluminum Ohms/kft
14 AWG15 A20 A25 A3.07 ohms5.06 ohms
12 AWG20 A25 A30 A1.93 ohms3.18 ohms
10 AWG30 A35 A40 A1.21 ohms2.00 ohms
8 AWG40 A50 A55 A0.764 ohms1.26 ohms
6 AWG55 A65 A75 A0.491 ohms0.808 ohms
4 AWG70 A85 A95 A0.308 ohms0.508 ohms
2 AWG95 A115 A130 A0.194 ohms0.319 ohms
1/0 AWG125 A150 A170 A0.122 ohms0.201 ohms
2/0 AWG145 A175 A195 A0.0967 ohms0.159 ohms
4/0 AWG195 A230 A260 A0.0608 ohms0.100 ohms

Copper vs aluminum wiring considerations

Aluminum wire has approximately 60% higher electrical resistance than copper of the same gauge. Consequently, an aluminum conductor must typically be sized two AWG gauges larger than a copper conductor to carry the same electrical load. While copper is the standard choice for indoor 15A and 20A branch wiring, aluminum (especially modern 8000-series alloy) is universally favored for heavy 100A, 150A, and 200A underground service entrance cables and subpanel feeds due to massive cost savings and lighter weight.

Common mistakes in wire sizing

  • Ignoring the 80% continuous load rule. The NEC mandates that circuit breakers and conductors serving continuous loads (operating for 3 hours or more, such as EV chargers and space heaters) must be sized for 125% of the continuous load amperage.
  • Using 90 deg C ampacity for breakers. While THHN insulation is rated for 90 degrees C, standard residential circuit breakers and terminal lugs are only rated for 60 degrees C or 75 degrees C. You must size wire using the 60C or 75C column to prevent terminal overheating.
  • Failing to upsize the equipment grounding conductor. Under NEC 250.122(B), if ungrounded hot conductors are upsized for voltage drop, the equipment grounding conductor must also be upsized proportionally.
Advertisement
Common questions

Wire Size Calculator FAQ

Straight answers to the questions people ask most about this calculation.

What size wire do I need for a 20 amp circuit?

Under standard conditions, a 20-amp circuit requires a minimum of 12 AWG copper wire or 10 AWG aluminum wire. If the run exceeds 50 to 75 feet, upsize to 10 AWG copper to prevent voltage drop.

What size wire is needed for a 50 amp RV or EV charger?

A 50-amp circuit requires 6 AWG copper wire with 75C rated terminals, or 4 AWG aluminum wire. Because EV charging is a continuous load, electrical codes require a 50A circuit for a 40A continuous charger.

What is acceptable voltage drop under the NEC?

The NEC recommends a maximum voltage drop of 3% on branch circuits, and no more than 5% total drop across both the feeder and branch circuit combined.

Why does wire gauge get smaller as the wire gets thicker?

The American Wire Gauge (AWG) system is based on the number of drawing dies the wire was pulled through during manufacturing. More passes through smaller dies resulted in thinner wire and a higher gauge number.

How far can you run 10 AWG wire on a 30 amp circuit?

On a 240V 30-amp circuit, 10 AWG copper wire can run approximately 65 feet before voltage drop exceeds the 3% limit. For longer distances, upsize to 8 AWG copper.

Can I use aluminum wire in a house?

Modern 8000-series aluminum alloy is code-approved, safe, and cost-effective for large subpanel feeds, heavy heat pumps, and main service entrance cables. It is not used for 15A and 20A branch outlets.

What is the difference between NM-B (Romex) and THHN wire?

NM-B (Romex) is a jacketed multi-conductor cable used inside residential walls and framed ceilings. THHN consists of individual insulated conductors designed to be pulled through conduit raceways.

How does voltage affect wire size?

Higher voltage requires smaller wire for the same amount of power (watts = volts x amps). Doubling the voltage halves the current, which drastically reduces voltage drop and allows smaller conductors over long distances.