actual loss over run
RecommendedHow wire gauge sizing works under the NEC
Selecting the correct wire size for an electrical circuit is governed by two distinct criteria in the National Electrical Code (NEC):
- Ampacity (Thermal Limit): The conductor must have sufficient cross-sectional area to carry continuous and non-continuous circuit current without heating the insulation beyond its temperature rating (NEC Table 310.16).
- Voltage Drop (Efficiency & Performance): On long circuit runs, conductor resistance causes voltage to drop before reaching the electrical load. NEC Informational Notes 210.19(A) and 215.2(A)(1) recommend that voltage drop should not exceed 3% on branch circuits, or 5% across both feeder and branch circuits combined.
The correct wire gauge is always the larger of the two sizes required by ampacity and voltage drop.
Three Phase Voltage Drop = (1.732 x Distance ft x Amps x Resistance per 1,000 ft) / 1,000. Resistance values come from NEC Chapter 9 Table 8.
A worked wire gauge example
Suppose you are running a 120-volt, 20-amp single-phase circuit to a detached workshop or shed located 150 feet away using copper conductors, aiming for a maximum 3% voltage drop.
- Ampacity check: A 20-amp circuit breaker requires a minimum 12 AWG copper wire (rated 25 amps at 75 deg C terminal rating).
- Resistance of 12 AWG copper: 1.93 ohms per 1,000 feet (NEC Table 8).
- Voltage drop on 12 AWG: (2 x 150 ft x 20A x 1.93 ohms) / 1,000 = 11.58 Volts.
- Drop percentage: (11.58V / 120V) x 100 = 9.65%. This vastly exceeds the 3% limit (3.60V max). Connected power tools would overheat and stall.
- Upsizing to 10 AWG (1.21 ohms/kft): (2 x 150 x 20 x 1.21) / 1000 = 7.26V (6.05% drop - still too high).
- Upsizing to 8 AWG (0.764 ohms/kft): (2 x 150 x 20 x 0.764) / 1000 = 4.58V (3.82% drop - close, but still over 3%).
- Upsizing to 6 AWG (0.491 ohms/kft): (2 x 150 x 20 x 0.491) / 1000 = 2.95V (2.46% drop).
- Final selection: Use 6 AWG copper wire. Voltage drop is reduced to 2.46%, delivering 117.05 volts to the shed.
Standard AWG ampacity and properties table
Extracted from NEC Table 310.16 and Chapter 9 Table 8 for copper and aluminum conductors:
Copper vs aluminum wiring considerations
Aluminum wire has approximately 60% higher electrical resistance than copper of the same gauge. Consequently, an aluminum conductor must typically be sized two AWG gauges larger than a copper conductor to carry the same electrical load. While copper is the standard choice for indoor 15A and 20A branch wiring, aluminum (especially modern 8000-series alloy) is universally favored for heavy 100A, 150A, and 200A underground service entrance cables and subpanel feeds due to massive cost savings and lighter weight.
Common mistakes in wire sizing
- Ignoring the 80% continuous load rule. The NEC mandates that circuit breakers and conductors serving continuous loads (operating for 3 hours or more, such as EV chargers and space heaters) must be sized for 125% of the continuous load amperage.
- Using 90 deg C ampacity for breakers. While THHN insulation is rated for 90 degrees C, standard residential circuit breakers and terminal lugs are only rated for 60 degrees C or 75 degrees C. You must size wire using the 60C or 75C column to prevent terminal overheating.
- Failing to upsize the equipment grounding conductor. Under NEC 250.122(B), if ungrounded hot conductors are upsized for voltage drop, the equipment grounding conductor must also be upsized proportionally.