RecommendedUnderstanding off-grid battery sizing: Watt-Hours, Amp-Hours, and Usable Capacity
Designing an off-grid electrical system for an RV, camper van, remote cabin, or marine vessel requires balancing daily energy demand with reliable energy storage. Unlike grid-tied systems that use the utility company as an infinite buffer, an off-grid system relies entirely on its battery bank when the sun is not shining or generator fuel is conserved. Accurately sizing a battery bank prevents power outages and ensures you do not permanently damage expensive battery cells through excessive discharge.
Battery capacity is measured in both kilowatt-hours (kWh) and amp-hours (Ah). While appliance power consumption is expressed in Watts or kilowatt-hours, battery banks are traditionally rated in amp-hours at a specific DC voltage (typically 12V, 24V, or 48V). The relationship between the two is simple: Watt-hours equals amp-hours multiplied by system voltage (Wh = Ah x V). For example, a 100 Ah battery at 12 Volts stores 1,200 Watt-hours (1.2 kWh) of gross energy.
Total Bank Wh = Usable Wh / Depth of Discharge (DoD). Total Bank Ah = Total Bank Wh / System Voltage (V). Recommended Solar Array = (Daily Wh / (Winter Sun Hours x 0.75 System Derate)).
Comparing battery chemistries: LiFePO4 Lithium vs AGM Lead-Acid
The single most important variable in battery bank sizing is depth of discharge (DoD). Depth of discharge is the percentage of a battery's total rated capacity that can be safely used without degrading cell health or shortening cycle life.
Traditional lead-acid batteries, including AGM (Absorbent Glass Mat) and Gel deep-cycle batteries, should never be discharged past 50 percent of their rated capacity. Discharging an AGM battery to 80 percent or 100 percent will cause rapid sulfation, dropping its usable lifespan from 500 cycles to fewer than 150 cycles. Consequently, if you need 200 amp-hours of usable energy, an AGM battery bank must be sized at 400 amp-hours.
In contrast, modern Lithium Iron Phosphate (LiFePO4) batteries support an 80 to 90 percent depth of discharge and deliver 3,000 to 5,000 cycles. LiFePO4 batteries also maintain a steady 13.0V to 13.2V voltage curve under heavy loads, whereas lead-acid batteries suffer from Peukert effect voltage sag when running high-draw appliances like microwaves or induction cooktops.
A worked off-grid battery bank calculation example
Suppose you are outfitting an off-grid camper van with a 12-Volt DC electrical system. Your daily appliance audit (compressor fridge, LED lights, laptop charging, water pump, and fan) totals 2.4 kWh per day (2,400 Watt-hours). You require 2 days of autonomy for stormy weather, using LiFePO4 lithium batteries and a 90 percent efficient pure sine wave inverter.
- Daily energy including inverter losses: 2,400 Wh / 0.90 efficiency = 2,667 Wh per day.
- Total usable energy for 2 days of autonomy: 2,667 Wh x 2 days = 5,334 usable Watt-hours.
- Nameplate battery bank size with 80% DoD: 5,334 Wh / 0.80 = 6,668 Watt-hours (6.67 kWh).
- Amp-hours at 12 Volts: 6,668 Wh / 12V = 556 Amp-hours.
- Battery modules to purchase: 556 Ah / 100 Ah per module = 5.56, rounded up to 6 x 100 Ah 12V LiFePO4 batteries (or 3 x 200 Ah batteries).
- Solar array to recharge in 4 peak sun hours: 2,667 Wh / (4.0 hours x 0.75 real-world derate) = 889 Watts, meaning a 900W to 1,000W rooftop solar array is required.
System voltage selection: 12V vs 24V vs 48V
Choosing the correct DC bus voltage is critical as system size grows. Power loss and wire heating are governed by current (Amps). Because Watts equals Volts multiplied by Amps, doubling system voltage cuts the current in half for the exact same power. A 3,000-Watt inverter running at 12 Volts draws a massive 250 Amps from the battery bank, requiring thick 4/0 AWG welding cables and heavy 300A fuses. Running that same 3,000-Watt inverter at 24 Volts draws 125 Amps (using standard 1/0 AWG wire), and at 48 Volts it draws only 62.5 Amps (using easy-to-route 4 AWG wire). As a general rule: systems under 1,500 Watts can stay 12V; systems between 1,500W and 3,000W benefit from 24V; and systems over 3,000W should almost always be built on 48V.